VIII | BUILDING SERVICES PROTECTION | GENERAL INDUSTRIAL - FACTORY AND WORKSHOPS | |||
---|---|---|---|---|---|
A | BUILDING UTILITIES | COMPLYING WITH CHAPTER 9 NFPA 101 | |||
1 | GAS EQUIPMENT & RELATED PIPING | PROTECTION AS PER NFPA 54 & NFPA 58 | REQUIRED | ||
2 | ELECTRICAL SYSTEMS / ELECTRICAL EQUIPMENT ROOMS | ASS OR 2-HRS ENCLOSURE | REQUIRED | ||
SUBSTATION & SWITHGEARS | ATTACHED TO OCCUPIED BUILDINGS & | 3-HOURS FRR* or ASS | |||
STANDALONE: TRANSFORMER VAULT REQUIRED PROTECTION | 3-HOURS FRR* or 1-HOUR FRR* WITH ASS | ||||
3 | COMMERCIAL COOKING EQUIPMENT | COMPLYING WITH NFPA 96 | REQUIRED | ||
KITCHEN/PANTRY ENCLOSURE | NOT REQUIRED | ||||
4 | ELEVATORS, ESCALATORS & CONVEYORS | COMPLYING WITH ASME A17.1/CSA B44 | REQUIRED | ||
FIRE FIGHTERS' EMERGENCY OPERATION | COMPLYING WITH ASME A17.1/CSA B44 | REQUIRED | |||
B | RUBBISH CHUTE, INCINERATORS & LAUNDRY CHUTES | COMPLYING WITH NFPA 82 | REQUIRED | ||
ENCLOSURES | ≤3 STOREYS / >3 STOREYS | 1-HOUR FRR* / 2-HRS FRR* | |||
OPENING PROTECTIVE | ≤3 STOREYS / >3 STOREYS | 1-HOUR FPR** / 1.5-HR FPR** | |||
LOW HAZARD | ORDINARY | ||||
C | EMERGENCY POWER SUPPLY SYSTEM | COMPLYING WITH NFPA 110 | NOT REQUIRED | REQUIRED | |
1 | GENERATORS | ENCLOSURE | 1-HOUR FRR* | 1-HOUR FRR* | |
D | FIRE PUMP ROOM | COMPLYING WITH NFPA 20 | REQUIRED | ||
PUMP ROOM ENCLOSURES | MORE THAN 15.3 M FROM ANY BUILDING | 1-HOUR FRR* | |||
WITHIN 15.3 M OR ATTACHED TO BUILDINGS | 2-HOURS FRR* | ||||
DIRECT SAFE ACCESS | EXTERNAL ACCESS WITHIN THE LEVEL OF DISCHARGE | REQUIRED | |||
WITHIN 3M FROM ANY EXIT THAT COMPLIES WITH DIRECT DISCHARGE REQUIREMENTS | PERMITTED | ||||
ACCESS COMPONENT (UNDERGROUND LOCATION) | STANDARD STAIR (NON-COMBUSTIBLE MATERIAL) | REQUIRED | |||
CAT STEEL LADDER | NOT PERMITTED | ||||
E | FIRE WATER TANKS | COMPLYING WITH NFPA 22 | REQUIRED | ||
MATERIALS | NON-COMBUSTIBLE MATERIAL | REQUIRED | |||
GRP TANKS (WITHIN 1-HR FIRE RATED ENCLOSURE) | PERMITTED | ||||
DESIGN/COMPARTMENTATION | TWO (2) COMPARTMENTS | REQUIRED | |||
F | SMOKE CONTROL / EMERGENCY VENTILATION | COMPLYING WITH NFPA 92 & NFPA 204 | REQUIRED | ||
1 | VENTILATION / SMOKE CONTROL SYSTEM BY ANY OF THE FOLLOWING; 1.1 NATURAL VENTILATION; 1.2 MECHANICAL VENTILATION & SMOKE CONTROL SYSTEM AND/OR 1.3 MECHANICAL VENTILATION BY POSITIVE VENTILATION (PRESSURIZATION) SYSTEM |
LOW HAZARD | ORDINARY | ||
FIRE AREA EXCEEDING 1,115 SQM | NOT REQUIRED | REQUIRED | |||
TOTAL AREA OF ALL FLOORS EXCEEDS 2,230 SQM | NOT REQUIRED | REQUIRED | |||
WOODWORKING OPERATIONS EXCEEDING 232 SQM | REQUIRED | ||||
POWER GENERATION BUILDING | REQUIRED | ||||
EXIT STAIRCASES CONNECTS MORE THAN FIVE (5) STORIES (LEVELS) INCLUDING THE BASEMENTS | REQUIRED | ||||
AND/OR WHEN SMOKE STOP &/OR FIRE FIGHTING LOBBIES ARE REQUIRED | REQUIRED | ||||
G | AIR-CONDITIONING & VENTILATION SYSTEM | COMPLYING WITH NFPA 90A & NFPA 90B | REQUIRED |