| IV | MEANS OF EGRESS | TYPE-C MERCANTILE | |||
|---|---|---|---|---|---|
| FIRE SAFETY PROVISIONS | MINIMUM REQUIREMENTS | ||||
| A | MEANS OF EGRESS GENERAL REQUIREMENTS | ||||
| 1 | SEPARATION OF MEANS OF EGRESS | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | ||
| EXIT ACCESS CORRIDORS | SERVING AN AREA HAVING AN OCCUPANT LOAD EXCEEDING 30 | 1-HR FRR* | |||
| EXITS | CONNECTS 3 OR FEWER STORIES | 1-HR FRR* | |||
| CONNECTS 4 OR MORE STORIES | 2-HRS FRR* | ||||
| OPENING PROTECTIVE | FIRE DOOR ASSEMBLIES EQUIPPED WITH DOOR CLOSERS | REQUIRED | |||
| CONSTRUCTION | LIMITED OR NON-COMBUSTIBLE MATERIALS | REQUIRED | |||
| OPENINGS AND PENETRATIONS IN EXIT ENCLOSURE | COMPLYING WITH CHAPTER 7 NFPA 101 | PERMITTED | |||
| 2 | EXITS HEADROOM | NOT LESS THAN 2285MM | REQUIRED | ||
| HEADROOM ON STAIRS | NOT LESS TAHN 2285MM | REQUIRED | |||
| 3 | WALKING SURFACES IN THE MEANS OF EGRESS | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | ||
| 4 | CHANGES IN LEVEL IN THE MEANS OF EGRESS | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | ||
| 5 | GUARDS | PROVIDED AT THE OPEN SIDES OF MEANS OF EGRESS 760MM ABOVE THE FLOOR OR FINISHED GROUND LEVEL | REQUIRED | ||
| 6 | IMPEDIMENT TO EGRESS | NOT PERMITTED | |||
| 7 | MEANS OF EGRESS RELIABILITY | CONTINUOUSLY MAINTAINED FREE OF ALL OBSTRUCTION OR IMPEDIMENTS | REQUIRED | ||
| FURNISHING AND DECORATION | FURNITURES, MOVABLE OBJECTS, MIRRORS, ETC. | NOT PERMITTED | |||
| B | MEANS OF EGRESS COMPONENTS | ||||
| 1 | FIRE DOORS | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | ||
| SIDE-HINGE OR PIVOTED-SWINGING TYPE | ANY DOOR ASSEMBLY IN A MEANS OF EGRESS | REQUIRED | |||
| MINIMUM DOOR LEAF WIDTH | 810MM | ||||
| HORIZONTAL SLIDING DOORS | COMPLYING WITH CHAPTER 7 NFPA 101 | PERMITTED | |||
| VERTICAL ROLLING DOORS | COMPLYING WITH CHAPTER 7 NFPA 101 | PERMITTED | |||
| REVOLVING DOORS / POWERED DOORS | COMPLYING WITH CHAPTER 7 NFPA 101 | PERMITTED | |||
| SELF-CLOSING DEVICES | DOORS REQUIRED TO BE NORMALLY KEPT CLOSED | REQUIRED | |||
| 2 | STAIRS | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | ||
| STANDARD STAIRS | FEWER THAN 50 PERSON (CLEAR WIDTH) | 915MM | |||
| <2000 PERSON (CLEAR WIDTH) | 1120MM | ||||
| >2000 PERSON (CLEAR WIDTH) | 1420MM | ||||
| SPIRAL STAIRS | COMPLYING WITH CHAPTER 7 NFPA 101 | PERMITTED | |||
| CURVE STAIRS | COMPLYING WITH CHAPTER 7 NFPA 101 | PERMITTED | |||
| WINDERS | COMPLYING WITH CHAPTER 7 NFPA 101 | NOT PERMITTED | |||
| GUARDS AND HANDRAILS | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | |||
| ENCLOSURE AND PROTECTION OF STAIRS | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | |||
| ENCLOSURES | ALL INTERIOR STAIRS SERVING AS AN EXIT COMPONENT | REQUIRED | |||
| DOORS FPR* | < 3 STOREYS / > 3 STOREYS | 1-HR FPR** / 1.5-HR FPR** | |||
| ENCLOSURES FRR* | < 3 STOREYS / > 3 STOREYS | 1-HR FRR** / 2-HRS FRR* | |||
| ENCLOSURE EXEMPTION | PENETRATING ONE FLOOR LEVEL OR SERVING MEZZANINE ONLY | PERMITTED | |||
| EXPOSURES | WALLS AND OPENINGS WITHIN 3050MM HORIZONTALLY OF AN EXTERIOR STAIRWAY ENCLOSURE | 1-HR FRR* | |||
| USABLE SPACE | WITHIN EXIT ENCLOSURE | NOT PERMITTED | |||
| LOCATION UNDER STAIRS IN ACCORDANCE WITH NFPA 101 | PERMITTED | ||||
| STAIRWAY IDENTIFICATION | SERVING 3 OR MORE STOREYS | REQUIRED | |||
| EXIT STAIR PATH MARKINGS | ALL STAIR COMPONENTS | REQUIRED | |||
| PERIMETER DEMARCATION MARKING | COMPLYING WITH NFPA 101 | REQUIRED | |||
| LOCK, LATCHES & ALARM DEVICES | COMPLYING WITH NFPA 101 | PERMITTED | |||
| RE-ENTRY PROVISIONS | LOCKED STAIRS EXCEEDING 4 STOREYS | NOT REQUIRED | |||
| 3 | RAMPS | COMPLYING WITH CHAPTER 7 NFPA 101 | PERMITTED | ||
| AS SECONDARY EXIT FOR ONE (1) BASEMENT LEVEL | PERMITTED | ||||
| 4 | ROOF ACCESS | BUILDING EQUAL OR MORE THAN 4 STOREYS (G+3) OR ROOFS 12M ABOVE GRADE PLANE | NOT REQUIRED | ||
| WHERE OPEN STAIR/S ARE PERMITTED AND PROVIDED IN TYPE B AND TYPE C MERCANTILE OCCUPANCY | NOT REQUIRED | ||||
| ONE AT EACH 9300 SQM ROOF AREA OR FLAT ROOFS OR ROOF PITCH <3 IN 12 | NOT REQUIRED | ||||
| ROOF ACCESS COMPONENTS | SMOKE VENTS (FIXED WALL OPENING/S) AT THE TOP OF THE STAIRWELL WITH A MINIMUM AREA OF 1.5 SQM | NOT REQUIRED | |||
| STAIR ACCESS TO ROOF PROVIDED WITH OPERABLE DOORS | NOT REQUIRED | ||||
| 5 | SMOKE PROOF ENCLOSURES | FRR - FIRE RESISTANCE RATING / FRP - FIRE PROTECTION RATING | |||
| STAIR ENCLOSURES | ALL INTERIOR STAIRS SERVING AS AN EXIT COMPONENT | REQUIRED | |||
| OPEN STAIR PENETRATING ONE (1) FLOOR / LEVEL ONLY | PERMITTED | ||||
| FIRE FIGHTING LOBBY (F/F LOBBY) | IN EVERY FIRE LIFT PROVISIONS | REQUIRED IN EVERY FIRE LIFT PROVISIONS | |||
| ADJACENT AND ACCESIBLE TO AN EXIT STAIRCASE | |||||
| SERVES AS A COMMON LOBBY FOR BOTH FIRE LIFT AND THE ADJACENT EXIT STAIRCASE | |||||
| 6 SQM MINIMUM AREA ( 2.0M LEAST SIDE DIMENSIONS) | |||||
| PROVISIONS AT THE LEVEL OF EXIT DISCHARGE | NOT REQUIRED | ||||
| SMOKE-STOP LOBBY (S/S LOBBY) | HIGH-RISE BUILDINGS WITH HABITABLE HEIGHT HIGHER THAN 28 METERS | NOT APPLICABLE | |||
| BASEMENT LEVEL/S EXCEED 9.0 M DEPTH | REQUIRED ON ALL FLOOR LEVELS | ||||
| BUILDING TRAVERSES MORE THAN FIVE (5) FLOOR LEVELS INCLUDING BASEMENT/S AND BELONGS TO A PLACE OF PUBLIC RESORT REGARDLESS OF THE HABITABLE HEIGHT. | NOT APPLICABLE | ||||
| 3 SQM MIN. AREA (LEAST SIDE DIMENSION 1.8M) | REQUIRED | ||||
| PROVISIONS AT THE LEVEL OF EXIT DISCHARGE | NOT APPLICABLE | ||||
| S/S & F/F LOBBY DOORS & WALL ENCLOSURES | 1.5-HR FPR** FIRE PROTECTION RATING/ FRR* 2-HRS FIRE RESISTANCE RATING | REQUIRED | |||
| 6 | HORIZONTAL EXITS | COMPLYING WITH CHAPTER 7 NFPA 101 | PERMITTED | ||
| 7 | EXIT PASSAGEWAYS | ENCLOSURE AND SEPARATION FIRE RESISTANCE RATING COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | ||
| MIN. WIDTH NOT LESS THAN 2/3 OF THE WIDTH OF THE EXIT STAIR | REQUIRED | ||||
| 8 | ESCALATORS & MOVING WALKS | AS PART OF THE REQUIRED MEANS OF EGRESS | NOT PERMITTED | ||
| 9 | FIRE ESCAPE STAIRS | COMPLYING WITH CHAPTER 7 NFPA 101 | PERMITTED | ||
| 10 | FIRE ESCAPE LADDERS | COMPLYING WITH CHAPTER 7 NFPA 101 | PERMITTED | ||
| 11 | SLIDE ESCAPES | COMPLYING WITH CHAPTER 7 NFPA 101 | PERMITTED | ||
| 12 | ALTERNATING TREAD DEVICES | COMPLYING WITH CHAPTER 7 NFPA 101 | PERMITTED | ||
| 13 | AREAS OF REFUGE | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | ||
| 14 | ELEVATORS | AS PART OF THE REQUIRED MEANS OF EGRESS | NOT PERMITTED | ||
| AS SECOND MEANS OF EGRESS FROM A TOWER AND COMPLYING WITH ASME A17.1/CSA B44 | NOT APPLICABLE | ||||
| ELEVATOR DOORS | OPENING INTO EXIT ENCLOSURES | NOT PERMITTED | |||
| C | CAPACITY OF MEANS OF EGRESS | ||||
| 1 | OCCUPANT LOAD | SALES AREA ON STREET FLOOR | 2.8 SQM / PERSON | ||
| SALES AREA ON 2 OR MORE STREET FLOORS | 3.7 SQM / PERSON | ||||
| SALES AREA ON FLOOR BELOW STREET FLOOR | 2.8 SQM / PERSON | ||||
| SALES AREA ON FLOORS ABOVE STREET FLOORS | 5.6 SQM / PERSON | ||||
| FLOORS OR PORTIONS OF FLOORS USED ONLY FOR STORAGE, RECEIVING AND SHIPPING AND NOT OPEN TO GENERAL PUBLIC. | 27.9 SQM / PERSON | ||||
| 2 | EGRESS CAPACITY | NFPA 101 TABLE 7.3.3.1 CAPACITY FACTORS | REQUIRED | ||
| STREET FLOOR EXITS | SIZE: STREET FLOOR PLUS THE REQ'D CAPACITY OF ALL STAIRS & RAMPS DISCHARGING ONTO THE STREET FLOOR | REQUIRED | |||
| AISLES (LEADING DIRECTLY TO EXIT) | WIDTH > REQUIRED WIDTH OF EXIT | REQUIRED | |||
| CLEAR WIDTH 915 MM | REQUIRED | ||||
| NOT LESS THAN 1 WITH 1525 MM WIDTH | REQUIRED | ||||
| CARTS & BUGGIES | ADEQUATE PROVISION FOR TRANSIT & PARKING | REQUIRED | |||
| D | NUMBER OF EXITS | ||||
| 1 | SINGLE EXIT | IN MEZZANINES WITH EXIT TRAVEL WITHIN COMMON PATH LIMIT | PERMITTED | ||
| IN ANY SECTION WITH EXIT TRAVEL WITHIN COMMON PATH LIMIT | PERMITTED | ||||
| 2 | NOT LESS THAN 2 SEPARATE EXITS | 50 - 500 OCCUPANTS | REQUIRED | ||
| ON EVERY STORY AND ACCESIBLE FROM EVERY PART OF EVERY STORY | REQUIRED | ||||
| 3 | NOT LESS THAN THREE (3) SEPARATE EXITS | EQUAL OR MORE THAN 500 OCCUPANTS | REQUIRED | ||
| 4 | NOT LESS THAN FOUR (4) SEPARATE EXITS | EQUAL OR MORE THAN 1000 OCCUPANTS | REQUIRED | ||
| E | ARRANGEMENT OF EXITS | NS*-NOT SPRINKLERED / S**-SPRINKLERED | NS* | S** | |
| 1 | TRAVEL DISTANCE | NFPA 101 TABLE A.7.6 | 23M | 30M | |
| 2 | COMMON PATH LIMIT | NFPA 101 TABLE A.7.6 | 23M | 30M | |
| 3 | DEAD-END CORRIDOR | NFPA 101 TABLE A.7.6 | 6.1M | 15M | |
| 4 | EXIT DISCHARGE | ||||
| EXTERIOR DISCHARGE (DIRECT TO BUILDING EXTERNAL) | COMPLYING WITH NFPA 101 | REQUIRED | |||
| THROUGH AREAS ON LEVEL OF EXIT DISCHARGE (INTERNAL DISCHARGE) | MAXIMUM 10M TRAVEL DISTANCE TO BUILDING EXTERNAL | PERMITTED | |||
| 50% OF THE REQUIRED NUMBER OF EXITS & 50% OF THE REQUIRED EXIT CAPACITY (SPRINKLER PROTECTED) | PERMITTED | ||||
| 5 | EXTERIOR WAYS OF EXIT | COMPLYING WITH NFPA 101 | PERMITTED | ||
| 6 | ACCESIBLE MEANS OF EGRESS | EXIT PROVISIONS FOR PEOPLE WITH SEVERE MOBILITY IMPAIRMENT | REQUIRED | ||
| NOT LESS THAN 2 EXITS | |||||
| 7 | ILLUMINATION OF MEANS OF EGRESS | COMPLYING WITH CHAPTER 7 NFPA 101 | NOT REQUIRED | ||
| 8 | EMERGENCY LIGHTING | THE BUILDING IS THREE (3) OR MORE STORIES IN HEIGHT | NOT REQUIRED | ||
| THE OCCUPANCY IS SUBJECT TO 50 OR MORE OCCUPANTS ABOVE OR BELOW THE LEVEL OF EXIT DISCHARGE | REQUIRED | ||||
| THE OCCUPANCY IS SUBJECT TO 300 OR MORE TOTAL OCCUPANTS | REQUIRED | ||||
| 9 | MARKINGS OF MEANS OF EGRESS | COMPLYING WITH CHAPTER 7 NFPA 101 | REQUIRED | ||
| F | SPECIAL MEANS OF EGRESS PROVISIONS | ||||
| 1 | FIREMEN ACCESS PANELS | HABITABLE HEIGHT EXCEEDING 10M | NOT REQUIRED | ||
| 2 | REFUGE FLOORS | HIGH-RISE BUILDING EXCEEDING 30 STORIES | NOT REQUIRED | ||
| 3 | ELEVATORS FOR OCCUPANT CONTROLLED EVACUATION PRIOR TO PHASE 1 EMERGENCY RECALL OPERATIONS | COMPLYING WITH CHAPTER 7 NFPA 101 | PERMITTED | ||