VI | FEATURES OF FIRE PROTECTION (NFPA 5000 TABLES 7.2.1.1, 7.3.2.1, 7.3.5 (a), (b), 7.3.5.5, 7.4.1) | TYPE-C MERCANTILE | ||
---|---|---|---|---|
A | CONSTRUCTION | COMPLYING WITH CHAPTER 7 & 8 OF NFPA 5000 | ||
1 | CONSTRUCTION (NON-COMBUSTIBLE OR LIMITED COMBUSTIBLE MATERIALS) |
TYPE I OR TYPE II | EXTERIOR BEARING WALLS | HOURLY RATINGS REQUIRED PER TYPE OF CONSTRUCTION BASED ON NFPA 5000 HEIGHT & AREA REQUIREMENTS |
FRAMING, COLUMNS, BEAMS, GIRDERS, TRUSSES | ||||
FLOOR CONSTRUCTION | ||||
B | COMPARTMENTATION / SUBDIVISION OF BUILDING SPACES | COMPLYING WITH NFPA 101 & NFPA 5000 | REQUIRED | |
1 | FIRE BARRIERS | COMPLYING WITH NFPA 101 & NFPA 5000 | REQUIRED | |
TENANT SPACES | SPRINKLER PROTECTED OR NON-SPRINKLER PROTECTED | NOT REQUIRED | ||
STORAGE AREAS | SPRINKLER PROTECTED | NOT REQUIRED | ||
NON-SPRINKLER PROTECTED | 1-HR FRR* | |||
2 | SEPARATION FROM OTHER OCCUPANCIES | AS PER NFPA 101 TABLE 6.1.14.4.1 (a), (b) | REQUIRED | |
MERCANTILE (BULK AND MALLS) | SPRINKLER PROTECTED | 1-HR FRR* | ||
NON-SPRINKLER PROTECTED | 2-HRS FRR* | |||
STORAGE (LOW/ORDINARY & HIGH HAZARD) | SPRINKLER PROTECTED | 1-HR FRR* | ||
NON-SPRINKLER PROTECTED | 2-HRS FRR* | |||
3 | CORRIDORS RATED SEPARATION | COMPLYING WITH NFPA 101.30 &31 | REQUIRED | |
REQUIRED SEPARATION | SPRINKLER PROTECTED | NOT REQUIRED | ||
NON-SPRINKLER PROTECTED | 1-HR FRR* | |||
4 | SMOKE PARTITIONS | COMPLYING WITH NFPA 101 & NFPA 5000 | NOT REQUIRED | |
5 | SMOKE BARRIERS | COMPLYING WITH NFPA 101 & NFPA 5000 | NOT REQUIRED | |
C | VERTICAL OPENINGS PROTECTION | PROTECTION COMPLYING WITH NFPA CODES | REQUIRED | |
1 | COMMUNICATING SPACES | COMPLYING WITH CHAPTER 8 NFPA 101 | PERMITTED | |
2 | ATRIUMS | COMPLYING WITH CHAPTER 8 NFPA 101 | PERMITTED | |
3 | CONVENIENCE OPENINGS | COMPLYING WITH CHAPTER 8 NFPA 101 | PERMITTED | |
4 | SHAFTS | COMPLYING WITH CHAPTER 8 NFPA 101 | PERMITTED | |
5 | MEZZANINES | COMPLYING WITH CHAPTER 8 NFPA 101 | PERMITTED | |
6 | CONCEALED SPACES & DRAFTSTOPS | COMPLYING WITH CHAPTER 8 NFPA 101 | REQUIRED | |
EXTERIOR & INTERIOR WALL & PARTITION | FIRE STOPPED AT EACH LEVEL, TOP STORY CEILING LEVEL & AT THE LEVEL OF SUPPORT FOR ROOFS | REQUIRED | ||
UNOCCUPIED ATTIC SPACES | DRAFTSTOPS INTO AREAS NOT EXCEEDING 280 SQM | REQUIRED | ||
CONCEALED SPACES (CEILINGS & FLOORS) | DRAFTSTOPS INTO AREAS NOT EXCEEDING 93 SQM | REQUIRED | ||
CONCEALED SPACES (FLOORS & ROOFS) | DRAFTSTOPS INTO AREAS NOT EXCEEDING 280 SQM | REQUIRED |