| 8 | BUILDING SERVICES PROTECTION (ASS* AUTOMATIC SUPPRESSION SYSTEM) | HIGH-RISE APARTMENT | ||
|---|---|---|---|---|
| A | BUILDING UTILITIES | COMPLYING WITH CHAPTER 9 NFPA 101 | REQUIRED | |
| 1 | GAS EQUIPMENT & RELATED PIPING | PROTECTION AS PER NFPA 54 & NFPA 58 | REQUIRED | |
| 2 | ELECTRICAL SYSTEMS | COMPLYING WITH NFPA 70 | REQUIRED | |
| ELECTRICAL EQUIPMENT ROOMS | AUTOMATIC SUPPRESSION SYSTEM OR 2-HOURS ENCLOSURE | REQUIRED | ||
| SUBSTATION & SWITHGEARS | ATTACHED TO OCCUPIED BUILDINGS REQUIRED PROTECTION | 3-HOURS FRR* or 2-HRS FRR & ASS* | ||
| STANDALONE TRANSFORMER VAULT REQUIRED PROTECTION | 3-HOURS FRR* or 1-HOUR FRR* & ASS | |||
| EXPLOSION PROTECTION (ENCLOSURES) | ASS* & 2-HOURS FRR* | |||
| 3 | COMMERCIAL COOKING EQUIPMENT | COMPLYING WITH NFPA 96 | NOT APPLICABLE | |
| KITCHEN/PANTRY | ENCLOSURES - FIRE RESISTANCE RATING (FRR*) | NOT REQUIRED | ||
| COOKING EQUIPMENT | EQUIPMENT USED ONLY FOR FOOR WARMING | NOT APPLICABLE | ||
| 4 | ELEVATORS, ESCALATORS & CONVEYORS | COMPLYING WITH ASME A17.1/CSA B44 | REQUIRED | |
| FIRE FIGHTERS' EMERGENCY OPERATION | COMPLYING WITH CHAPTER 9 NFPA 101 & ASME A17.1/CSA B44 | REQUIRED | ||
| B | RUBBISH CHUTE, INCINERATORS & LAUNDRY CHUTES | COMPLYING WITH NFPA 82 | REQUIRED | |
| ENCLOSURES | TRAVERSES EQUAL OR LESS THAN 3 STOREYS | 1-HOUR FRR* | ||
| TRAVERSES MORE THAN 3 STOREYS | 2-HOURS FRR* | |||
| OPENING PROTECTIVE | TRAVERSES EQUAL OR LESS THAN 3 STOREYS | 1-HOUR FPR** | ||
| TRAVERSES MORE THAN 3 STOREYS | 1.5-HOURS FPR** | |||
| C | EMERGENCY POWER SUPPLY SYSTEM | COMPLYING WITH NFPA 110 | REQUIRED | |
| 1 | GENERATORS | ENCLOSURE | 1-HOUR FRR* | |
| D | FIRE PUMP ROOM | COMPLYING WITH NFPA 20 | REQUIRED | |
| ENCLOSURES | MORE THAN 15.3 M FROM ANY BUILDING | 1-HOUR FRR* | ||
| WITHIN 15.3 M OR ATTACHED TO BUILDINGS | 2-HOURS FRR* | |||
| THROUGHOUT SPRINKLER (BUILDING/S & PUMP ROOM) | 1-HOUR FRR* | |||
| DIRECT SAFE ACCESS | EXTERNAL ACCESS WITHIN THE LEVEL OF DISCHARGE | REQUIRED | ||
| WITHIN 3M FROM ANY EXIT THAT COMPLIES WITH DIRECT DISCHARGE REQUIREMENTS | PERMITTED | |||
| ACCESS COMPONENT (UNDERGROUND LOCATION) | STANDARD STAIR (NON-COMBUSTIBLE MATERIAL) | REQUIRED | ||
| CAT STEEL LADDER | NOT PERMITTED | |||
| E | FIRE WATER TANKS | COMPLYING WITH NFPA 22 | REQUIRED | |
| WATER TANK MATERIALS | NON-COMBUSTIBLE MATERIAL | REQUIRED | ||
| GRP TANKS (WITHIN 1-HR FIRE RATED ENCLOSURE) | PERMITTED | |||
| DESIGN/COMPARTMENTATION | TWO (2) COMPARTMENTS | REQUIRED | ||
| F | SMOKE CONTROL / EMERGENCY VENTILATION | COMPLYING WITH NFPA 92 & NFPA 204 | REQUIRED | |
| 1 | VENTILATION BY ANY OF THE FOLLOWING; a. NATURAL VENTILATION; b. MECHANICAL VENTILATION BY POSITIVE VENTILATION (PRESSURIZATION) SYSTEM |
EXIT STAIRCASES CONNECTS MORE THAN FIVE (5) STOREYS (LEVELS) INCLUDING BASEMENT/S | REQUIRED | |
| AND/OR WHEN SMOKE-STOP &/OR FIRE FIGHTING LOBBIES ARE REQUIRED | REQUIRED | |||
| 2 | VENTILATION BY ANY OF THE FOLLOWING; a. NATURAL VENTILATION; b. MECHANICAL VENTILATION & SMOKE CONTROL SYSTEM |
BASEMENT LEVEL/S WITH FLOOR AREA (FA) EXCEEDING 500 SQM | REQUIRED | |
| VERTICAL OPENINGS, ATRIUMS & OTHER LARGE VOLUME OF SPACES | REQUIRED | |||
| G | AIR-CONDITIONING & VENTILATION SYSTEM | COMPLYING WITH NFPA 90A & NFPA 90B AND OTHER RELEVANT, APPLICABLE NFPA CODES & STANDARDS | REQUIRED | |