NFPA 101 – Required Number of Means of Exit by Occupancy Type

NFPA-101 Life Safety Code

Written by

in

,

Understanding the required number of means of exit is critical for building safety and NFPA 101 compliance. This quick-reference table summarizes the minimum number of exits required for different occupancy types based on the Life Safety Code.

Always verify with your local authorities and the latest edition of NFPA 101 for complete requirements.


Required Number of Means of Exit by Occupancy Type

Occupancy Type (New Building)Code ReferenceNumber of Means of Exit
AMBULATORY (Sprinklered or Not Sprinklered)(20.2.4 and 7.4)Minimum Two (2)
ASSEMBLY (Sprinklered or Not Sprinklered)(12.2.4 and 7.4)Minimum Two (2)
BUSINESS (Sprinklered or Not Sprinklered)(38.2.4 and 7.4)Minimum Two (2) on every storey
HEALTHCARE(18.2.4 and 7.4)Minimum Two (2) on every storey
EDUCATIONAL(14.2.4 and 7.4) (14.2.5.4)Minimum Two (2) on every storey. Room shall have at least Two (2) doors if area > 93 sqm or Occupant Load > 50 persons.
ONE & TWO FAMILY DWELLINGS(N/A)No Requirements
HOTELS AND DORMITORIES(28.2.4 and 7.4)Minimum Two (2) on every storey
APARTMENTS(30.2.4 and 7.4)Minimum Two (2)
MERCANTILE(36.2.4 and 7.4)Minimum Two (2) on every storey
STORAGE(42.2.4 and 7.4)Single Exit allowed in Low hazard occupancy. Single Exit allowed in Ordinary hazard occupancy on condition that distance to exit is within the permitted Common Path of Travel distance. Minimum Two (2) if otherwise the above.
INDUSTRIAL(40.2.4.1.1)Minimum Two (2) on every storey and not less than one exit shall be reached without traversing another storey.

Building evacuation floor plan with marked exit routes

 


NFPA 101 – 7.4.1.2

The number of Room Exits or Storey Exits, other than for existing buildings permitted in Chapters 12 through 42, shall be as follows:

Occupant LoadMinimum Number of Exits
More than 500 but not more than 1000Not less than 3
More than 1000Not less than 4

NFPA Xchange Community Discussions

For more insights and discussions on means of egress requirements, visit the NFPA Xchange community:


Disclaimer

  • Code Reference: NFPA 101 2012 edition unless otherwise noted.

  • Purpose: This information is not complete and is intended as a quick reference only. Always refer to the full NFPA 101 code or your local codes for complete and up-to-date requirements.

  • Professional Advice: This content is for informational purposes only and should not replace professional fire safety consultation or legal advice.