OCCUPANCY TYPE (new building) |
CODE REF. | FURNITURE & MATTRESSES TESTS |
AMBULATORY (Not Sprinklered) |
(20.7.5.2, 20.7.5.3) | The Furnitures shall meet the criteria in 10.3.2.1 and 10.3.3. The Mattresses shall meet the criteria in 10.3.2.2 and 10.3.4. |
AMBULATORY (Sprinklered) |
(20.7.5.2, 20.7.5.3) | Exempted from requirement of 10.3.2 |
ASSEMBLY (Sprinklered and not sprinklered) |
(12.7.4.5) | Furnitures and Mattresses are not required to meet criteria of 10.3.2 (cigarette ignition resistance) |
BUSINESS (Sprinklered and Not Sprinklered) |
(12.7.4) | Furnitures and Mattresses are not required to meet criteria of 10.3.2 (cigarette ignition resistance) |
DAYCARE (Sprinklered and Not Sprinklered) | (16.7.4.5) | Exempted from requirement of 10.3.2 |
HEALTHCARE (Sprinklered) |
(18.7.4.4) | Exempted from requirement of 10.3.2 |
EDUCATIONAL (Not Sprinklered) |
(14.7.4.4) | Comply to requirement of 10.3.2.1 and 10.3.2.2 |
EDUCATIONAL (Sprinklered) |
(14.7.4.4) | Exempted from requirement of 10.3.2 |
ONE & TWO FAMILY DWELLINGS |
(24.3.3.4) | Exempted from requirement of 10.3.2 |
HOTELS AND DORMITORIES (Sprinklered and Not Sprinklered) |
(28.3.3.4.1) | Exempted from requirement of 10.3.2 |
APARTMENTS (Sprinklered and Not Sprinklered) |
(30.3.3.4.1) | Exempted from requirement of 10.3.2 |
MERCANTILE (Sprinklered and Not Sprinklered) |
(36.7.4.4) | Exempted from requirement of 10.3.2 |
STORAGE (Sprinklered and Not Sprinklered) |
(42.9) | Exempted from requirement of 10.3.2 |
INDUSTRIAL (Sprinklered and Not Sprinklered) | (40.7) | Exempted from requirement of 10.3.2 |
–
- Code Reference used is NFPA-101 2012 edition unless otherwise noted.
- These information is not complete and intended to be used as quick references only, always refer to NFPA or your local codes for complete information.