Portable Fire Extinguisher

Location Type of Extinguishers to be provided as a Set Maximum Travel Distance to nearest Extinguisher Set
Offices
  • Water Type, 9 Ltrs
  • CO2, 2 kg
15-m
Common Circulation Areas, Corridors, Lobbies, Passageways
  • Water Type, 9 Ltrs
  • CO2, 5 kg
22.5-m
Electrical Rooms, Telephone Rooms, Mechanical Plant Room, Lift Machine Room, Other Services Rooms
  • Dry Powder Type, 4.5 Kg
  • CO2, 5 kg
9-m
Parking Areas
  • Multipurpose (ABC) Dry Powder Type, 4.5 Kg
  • CO2, 2 kg
  • FFP Foam Trolley Type, 20 Gal.
15-m30-m along the driveway
Transformer Room
  • Dry Powder Type, 4.5 Kg
  • CO2, 5 kg
  • Dry Powder Trolley Type, 25 Kg per Transformer
9-m
HV / LV Room
  • Dry Powder Type, 4.5 Kg
  • CO2, 5 kg
  • Dry Powder Trolley Type, 12 Kg near exit
9-m
Diesel Generator Room
  • Dry Powder Type, 4.5 Kg
  • CO2, 5 kg
  • FFP Foam Trolley Type, 20 Gal. per DG set
9-m
Garbage Collection Room
  • Dry Powder Type, 6 Kg
9-m
Library
  • Water Type, 9 Ltrs
  • CO2, 2 kg
  • Dry Powder Type, 4.5 Kg
15-m
Laboratories
  • Water Type, 9 Ltrs
  • CO2, 2 kg
  • Dry Powder Type, 4.5 Kg
9-m
Gymnasium
  • Water Type, 9 Ltrs
  • Dry Powder Type, 4.5 Kg
15-m
Theater
  • Water Type, 9 Ltrs
  • CO2, 2 kg
  • Dry Powder Type, 4.5 Kg
15-m
Kitchen
  • CO2, 2 kg
  • Dry Powder Type, 4.5 Kg
  • Foam Extinguisher
9-m
Patient Rooms
  • Water Type, 9 Ltrs
  • CO2, 2 kg
  • Dry Powder Type, 4.5 Kg
15-m
Hotel
  • Water Type, 9 Ltrs
  • CO2, 2 kg
  • Dry Powder Type, 4.5 Kg
15-m