Electrical Room

Considering QCDD Guidelines;

As per QCD-GA 1.2, if Electrical room < 5.1sqm and with 2-hrs enclosure, then Automatic Suppression system is NOT required.

As per QCD-GA 1.2, if Electrical room > 5.1sqm, then Automatic Suppression system is required. The wall enclosure fire rating doesn’t need to be 2-hrs as per below table;

VIII BUILDING SERVICES PROTECTION (ASS* AUTOMATIC SUPPRESSION SYSTEM) ANY OCCUPANCY
A BUILDING UTILITIES COMPLYING WITH CHAPTER 9 NFPA 101
2 ELECTRICAL SYSTEMS COMPLYING WITH NFPA 70 REQUIRED
ELECTRICAL EQUIPMENT ROOMS AUTOMATIC SUPPRESSION SYSTEM OR 2-HOURS ENCLOSURE REQUIRED
SUBSTATION & SWITHGEARS ATTACHED TO OCCUPIED BUILDINGS REQUIRED PROTECTION 3-HOURS FRR* or ASS*
STANDALONE TRANSFORMER VAULT REQUIRED PROTECTION 3-HOURS FRR* or 2-HOURS FRR* with ASS
EXPLOSION PROTECTION ASS* & 2-HOURS FRR* ENCLOSURE

Considering NFPA 13;

  1. 8.15.10.3 Sprinklers shall not be required in electrical equipment rooms where all of the following conditions are met:
    (1) The room is dedicated to electrical equipment only.
    (2) Only dry-type electrical equipment is used.
    (3) Equipment is installed in a 2-hour fire-rated enclosure including protection for penetrations.
    (4) No combustible storage is permitted